Full Load Current at Cam Setting & Trip Settings:
A-184.6 to 276.8 A, Trip 2400
B-276.9 to 369.1 A, Trip 3600
C-369.2 to 553.70 A, Trip 4800
D-553.8 to 738.4 A, Trip 7200
E-738.5 to 923.0 A, Trip 9600
F-923.1 to 1107.6 A, Trip 12000
G-1107.7 to 1309.1 A, Trip 14400
Rated Current at 480Vac 42kA

Features:
The traditional system used for this purpose is based on three different devices:
a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching.
In particular, when selecting these devices, different factors must be taken into consideration, such as:
The motor power, The diagram and type of starting, The type of motor: with cage rotor or with wound rotor, The fault current at the point of the network where the motor is installed

offers a complete range of 3 pole Molded Case Motor Circuit Protectors (MCPs, magnetic or short circuit protection only) which are used to protect the cables feeding three phase motors in six frame sizes: M1M - 150 A, M2M - 250 A, M3M - 400 A, M4M - 600 A, M5M - 800 A, and M6M - 1200 A. Each frame size offers a range of interrupting ratings at 240-690 Vac and 250-600 Vdc. 5-Year limited warranty.

Additional Info

Brand Noark
Component Type Molded Case Circuit Protector
Noark Product Series Noark Ex9M6M
Number Of Poles 3